  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 64
Lock out (Status signals)
Status signals Description Probable causes Checking / solution
Error code 1
(1 times red
signal)
Sensor fault,
temperature fault or
flow fault
4 Sensor not or badly
connected
4 Bad connection
4 Non-existent or insufficient
circulation
4 Water circulation direction
reversed
4 Sensor fault
4 Check the wiring
4 Check that the sensors are operating correctly
4 Check that the sensor has been correctly fitted
4 Vent the air in the heating system
4 Check the water pressure
4 Check the cleanliness of the heat exchanger
4 Check the circulation (direction, pump, valves)
4 Replace the sensor if necessary
Error code 2
(2 times red
signal)
Maximum
temperature of heat
exchanger or control
unit exceeded
4 Non-existent or insufficient
circulation
4 Sensor not or badly
connected
4 Bad connection
4 Sensor fault
4 No air supply or insufficient
air supply
4 No flue gas flow or
insufficient flue gas flow
4 Circulation
4 Vent the air in the heating system
4 Check the water pressure
4 Check the cleanliness of the heat exchanger
4 Check the circulation (direction, pump, valves)
4 Check the wiring
4 Check that the sensors are operating correctly
4 Check that the sensor has been correctly fitted
4 Replace the sensor if necessary
4 Check air supply
4 Check flue gas flow
4 Replace seals
Error code 3
(3 times red
signal)
Ignition fault:
4 5 burner start-up
failures
4 False flame
signal
4 5x Flame loss
4 No ignition
4 Ignition arc, but no flame
formation
4 Presence of the flame but
insufficient ionization (<1
µA)
4 Check the wiring
4 Check breakdown to earth
4 Check the condition of the burner set
4 Check the earthing
4 Check that the gas valve is fully opened
4 Check the supply pressure
4 Purge the gas supply to remove air
4 Check the operation and setting of the gas valve
unit
4 Check that the air inlet and flue gas discharge
flues are not blocked
4 Replace the ionization/ignition electrode
Error code 4
(4 times red
signal)
Fan fault
4 External draught over the
boiler
4 Defective gas/air unit
4 Check for adequate draw on the chimney
connection
4 Replace the gas/air unit
Error code 5
(5 times red
signal)
Parameter error
4 Bad connection
4 Safety parameters not found
4 Check the wiring
4 Reset dF/dU code with a service tool
Error code 6
(6 times red
signal)
Miscellaneous
4 Several possible causes 4 Fault codes can be read using a service tool
EMC-M 24 EMC-M 24/28 MI EMC-M 30/35 MI EMC-M 34/39 MI 8. Troubleshooting