7.2.5. Checking the transfer capacity
If tap capacity falls significantly (due to insufficient temperature and/
or flow rate), clean the plate heat exchanger (hot water side) and the
tap water cartridge:
¼See chapter: "Cleaning the plate exchanger", page 56.
7.2.6. Checking the flue gas discharge and the air
supply
Check the tightness of the flue gases evacuation and air inlet
connections.
7.2.7. Checking combustion
Measure the O
2
/ CO
2
contents and the temperature of the flue gases
at the flue gas measuring point. To do this, proceed as follows:
4 Heat the water in the boiler to a temperature of approx. 70 °C.
4 Unscrew the plug of the flue gas measurement point.
4 Measure the smoke content in O
2
/ CO
2
using the measuring
equipment. Compare this with the control value.
¼See following chapters:
"Setting the air/gas ratio (Full load)", page 41
"Setting the air/gas ratio (Part load)", page 42
7.2.8. Checking the automatic air vent
1. Check that the automatic bleed is working (This is visible on the
right on top of the boiler).
2. The air vent can be closed off with the cap that can be found next
to it.
3. If any leaks are detected, replace the air vent.
R000406-A
T003127-B
R000350-A
7. Checking and maintenance